Title

15 High Rate Mixing Pump Shutdown

Typically, the High Rate Mixing Pumps run in automatic mode, 24 hours per day, seven days per week.

SOP Identification Number
SOP Identification Number:
1505_High Rate Mixing Pump Shutdown
Purpose and scope
Purpose and scope:

To shut down the pump(s) for repair or maintenance.

Health & Safety Warnings
Health & Safety Warnings:

Watch for open tanks and high elevations. If working on or near equipment, watch for rotating parts. Watch for tripping hazards and overhead piping while manipulating the valves.

Cautions
Cautions:

Use caution when rotating valves. Valves must be opened and closed in a particular order. The first step should always be to open a valve. If the operator’s first step is to close a valve, there is a risk that two valves on that pressure system may be closed. If this happens, pressure sensors should signal an alarm. The worst case scenario is that the high pressure created in the closed pressure system would cause damage and/or failure of the system.  Warning: always verify which valves are open and closed before making any changes.

Personnel Qualifications
Personnel Qualifications:

Operator I, knowledge of digestion process and equipment controls.

Equipment, Supplies, Required Tools
Equipment, Supplies, Required Tools:
  • Key or other tool to open/close valves.
Quality Control/Quality Assurance Activities for the Procedure
Quality Control/Quality Assurance Activities for the Procedure:
  • Record activity to log book.
Procedure
Procedure:

1.     Turn off pump control at the control panel. The High Rate Mixing Pump controls are located on MCC-5 in the Digester Control Building.

a.     Locate the Control Bucket {tag nos. 1505BKT5100 & 1505BKT5200} for the pump(s) to be stopped.

b.     Turn the On/Off Switch {tag no. 1505HS5100B & 1505HS5200B} to the OFF position.  The green indicator light should go out when the pump stops running.

c.     Place the Main Breaker {tag nos. 1505BKR5100 & 1505BKR5200} in the OFF position.

 

2.     Turn of f pump(s) at the local control switch.

a.     Each High Rate Mixing Pump is equipped with a push button Lock Out Switch (LOS) {tag nos. 1505HS5100A & 1505HS5200A} and a Disconnect Switch {tag nos. 1505HS5100 & 1505HS5200}.  Both switches are installed to a stantion, located adjacent to the pump.

b.     Turn the Disconnect Switch {tag nos. 1505HS5100 & 1505HS5200} to the OFF position.

c.     Place the Lock Out Switch {tag nos. 1505HS5100A & 1505HS5200A} in the “Stop” position by pushing the plunger in.

d.     Follow the Lock Out/Tag Out procedure for the pump. Click here for a copy of the procedure.

 

3.     Verify Suction and Discharge Valve Status.

a.     Each High Rate Mixing Pump system is equipped with two isolation suction valves: a bottom suction valve {tag no. 1505VLV5100 & 1505VLV5200) and a top suction valve {tag no. 1505VLV5100A & 1505VLV5200A}Locate the suction valve that is currently open and close that valve. Both isolation suction valves should now be closed.

b.     Each High Rate Mixing Pump is equipped with one isolation discharge valve {tag nos. 1505VLV5100F & 1505VLV5200F}.  Close the isolation discharge valve.    
 

4.     Observe High Rate Mixing Pump Operation:

a.     Listen for excessive noise or vibration.

b.     Check for oil or process fluid leaks.

 

5.     Record Data to Operator’s Log BookRecord High Rate Mixing Pump Activities to the log book with other entries for the day.  Include the following in the entry:

·         Operator(s) that performed the High Rate Mixing Pump SOP.

·         Note condition of equipment, piping, valves, etc.

·         Note any unusual conditions with flows, levels, odors or other process issues.

·         Note any damage, wear, or required maintenance on equipment.

Data & Records Management, Calculations, Forms, Reports
Data & Records Management, Calculations, Forms, Reports:
  • Update log book.
  • Update maintenance records (if applicable).
  • Report any maintenance or attention that is required.
Limits/Criteria for Data/Results
Limits/Criteria for Data/Results:

The pumps run constantly. 

Equipment
Equipment:

EQUIPMENT NAME

TAG NUMBER

High Rate Mixing Pump No. 1

1505PMP5100

High Rate Mixing Pump No. 1 Motor

1505MTR5100

High Rate Mixing Pump No. 1 – Bottom Isolation Valve

1505VLV5100

High Rate Mixing Pump No. 1 – Top Isolation Valve

1505VLV5100A

High Rate Mixing Pump No. 1 – Isolation Discharge Valve

1505VLV5100F

High Rate Mixing Pump No. 1- Suction Pressure Gauge

1505PI5100

High Rate Mixing Pump No. 1 - Disconnect Switch

1505HS5100

High Rate Mixing Pump No. 1 – Lock Out Switch

1505HS5100A

High Rate Mixing Pump No. 1 – Control Bucket

1505BKT5100

High Rate Mixing Pump No. 1 – Main Breaker

1505BKR5100

High Rate Mixing Pump No. 1 – On/Off Switch

1505HS5100B

High Rate Mixing Pump No. 1 – Indicator Light

1505HS5100C

High Rate Mixing Pump No. 2

1505PMP5200

High Rate Mixing Pump No. 2 Motor

1505MTR5200

High Rate Mixing Pump No. 2 – Bottom Isolation Valve

1505VLV5200

High Rate Mixing Pump No. 2 – Top Isolation Valve

1505VLV5200A

High Rate Mixing Pump No. 2 – Isolation Discharge Valve

1505VLV5200F

High Rate Mixing Pump No. 2- Suction Pressure Gauge

1505PI5200

High Rate Mixing Pump No. 2 - Disconnect Switch

1505HS5200

High Rate Mixing Pump No. 2 – Lock Out Switch

1505HS5200A

High Rate Mixing Pump No. 2 – Control Bucket

1505BKT5200

High Rate Mixing Pump No. 2 – Main Breaker

1505BKR5200

High Rate Mixing Pump No. 2 – On/Off Switch

1505HS5200B

High Rate Mixing Pump No. 2 – Indicator Light

1505HS5200C