14 DPS Surge Tank
During typical operation of the Reclaimed Water System, the DPS Pumps {tag no. 1404PMP4100, 1404PMP41200, 1404PMP4300, 1404PMP4400, 1404PMP45010} run in AUTO mode and the Surge Tank {tag no. 1404TNK4691}maintains the Reclaimed Water System pressure at 120 psi.
A Surge Tank Operation Table is posted on the DSPS Main Control Panel (click here for a copy of the table). The table lists critical DPS Surge Tank water depths, their corresponding system pressures, and actions to be performed by the operator. As noted on the Surge Tank Operation Table, a Surge Tank water level of 26” corresponds to the normal system pressure of 120 psi. Surge Tank water levels can be viewed at the Surge Tank Level Sensor Display {tag no. 1404LI4541}.
Under certain abnormal condition (such as extreme changes in flow, a break in the main line, etc.), it is possible for the Surge Tank water level to drop below 26”. Surge Tank water levels that fall below 26” correspond to low system pressure. Surge Tank water levels that fall below 10” require immediate action by the operator.
Low or Failed System Pressure Condition: The fastest way to get the system back in service is to re-pressurize the Surge Tank with the portable Smith compressor and manually run the DSPS pumps. Sometimes re-pressurizing the Surge Tank alone will not re-pressurize the entire system.
When the Surge Tank water level falls below 10”, the pressure sustaining valve closes. The pressure sustaining valve is located at the bottom of the Surge Tank and is a butterfly valve that is controlled by a three-way air solenoid. During normal pressure conditions, the solenoid switch is in the middle position.
This SOP is intended to restore normal pressure to the DPS system by re-pressurizing the Surge Tank.
- DPS: Distribution Pump Station
- If working on or near equipment, watch for rotating parts.
- Use extreme caution when working around pressurized systems.
- Ensure that timing of the SOP does not interfer with the current Reclaimed Water demand and distribution.
- Frequent switching on and off of variable speed pumps can damage the VFDs.
- If the Emqlo Compressor is used, be prepared to allow 3-4 hours to resume system pressure.
Under certain abnormal condition (such as extreme changes in flow, a break in the main line, etc.), it is possible for the Surge Tank water level to drop below 26”. Surge Tank water levels that fall below 26” correspond to low system pressure. Surge Tank water levels that fall below 10” require immediate action by the operator.
- The Equipment List/Tag No. List describes the Reclaimed Water System as the "Recycle Water System".
- The Operator must have access to a compressor.
- Operator I
- Knowledge of Distribution Pump Station System
- Knowledge of Reclamation Phase II System
- Knowledge of SCADA controls
- Click here for a copy of the Surge Tank Level Table.
- Access to the portable Smith Compressor or the Emqlo DPS Compressor.
Low or Failed System Pressure Condition: The fastest way to get the system back in service is to re-pressurize the Surge Tank with the portable Smith compressor and manually run the DSPS pumps. Sometimes re-pressurizing the Surge Tank alone will not re-pressurize the entire system.
When the Surge Tank water level falls below 10”, the pressure sustaining valve closes. The pressure sustaining valve is located at the bottom of the Surge Tank and is a butterfly valve that is controlled by a three-way air solenoid. During normal pressure conditions, the solenoid switch is in the middle position.
1. Re-Pressurize the System to 80 psi:
a. Place one of the DSPS variable speed pumps {tag no. 1404PMP/VSD4100 & 1404PMP/VSD4200} in manual control by turning the HOA switch {tag no. 1404HS4100 & 1404HS4200} to HAND. Depending on the current system demand, the operator may need to run one variable speed pump and one constant speed pump {tag nos. 1404PMP4200, 1404PMP4400 & 1404PMP4500}. If Phase 2 is filling or there is a leak in the system, etc., more pumping will be required to restore pressure in the system.
b. Monitor the Reclaimed Water system pressure on the local PLC screen. Manually increase the variable pump speed and/or run a constant speed pump if more flow is required to meet the target pressure.
2. Re-Pressurize the Surge Tank:
a. Move the portable Smith Compressor to the DPS Surge Tank {tag no. 1404TNK4691}. The portable Smith Compressor is typically stored in the Sludge Pump Room. If the Smith compressor is unavailable, substitute the Emqlo DPS Compressor {tag no. 1404CMP4841} (located in the DPS Control Room) to re-pressurize the Surge Tank. Please note: output from this compressor is very low and it can take 3 – 4 hours to resume system pressure.
b. Connect the compressor air hose to the Surge Tank connection, which is located overhead.
c. Force air until the Surge Tank pressure equals the Reclaimed Water system pressure.
d. Once the Surge Tank pressure and the Reclaimed Water system pressure are aligned, re-open the Pressure Sustaining Valve {tag no. 1404FY4691} by turning the 3-way switch. This will equalize the Surge Tank pressure and system pressure.
3. Re-Pressurize the System to 120 psi:
a. When the Reclaimed Water system pressure and Surge Tank pressure are equalized at 80 psi, place the DSPS pumps back in AUTO control at the HOA switch.
b. As the Reclaimed Water system pressure increases to 120 psi, refer to the Surge Tank Operation Table for further instructions. The Surge Tank Operation Table is taped to the front of the DSPS control panel. Click here for a copy of the Table.
DPS Compressor Operation:
If the Smith Compressor is unavailable, substitute the use Elmqo Compressor and perform the following SOP. Under normal conditions, the Elmqo DSPS Compressor {tag no. 1404CMP4841} runs in AUTO mode. The typical functions of the DSPS Compressor are the following:
· Provide air to the Pressure Sustaining Valve {tag no. 1404FY4691} on the Surge Tank.
· Provide a direct air source to the Surge Tank {tag no. 1404TNK4691}.
· Maintain a pressure of 120 – 160 psi in order to maintain a DPS system pressure of 120 psi.
Under normal conditions, the Air Supply Valve {tag no. 1404VLV46825} is closed. When the Surge Tank water level reaches 31 inches (an abnormal condition), the Air Supply Valve automatically opens and the Compressor {tag no. 1404CMP4841} forces air into the Surge Tank {tag no. 1404TNK4691} until the water level lowers to 26 inches. The Air Supply Valve will automatically close when the Surge Tank water level reaches 26 inches.
When the Surge Tank water level falls below 26 inches, the following SOP should be performed.
1. Open Air Supply Valve.
a. Locate the Air Supply Valve Switch {tag no. 1404HS4841}, which is located on the side of the main DPS Control Panel, below the blue keypad. During normal operating conditions (when the Surge Tank water level is at 26 inches) the Air Supply Valve is closed and the Switch is in the OFF position.
b. Flip the switch to OPEN. You should hear the air release as the valve is opened and air is pushed back into the Surge Tank {tag no. 1404TNK4691}.
The Surge tank control valve toggle switch should be in ON (auto) position. The switch is equipped with a safety feature that automatically closes the switch during a power outage. This feature saves air in the surge tank during power outages.
- Update log book.
- Update maintenance records (if applicable).
- Report any maintenance or attention that is required.
- Demand for the Reclamation Water System is unaffected by performing this SOP.
- The Surge Tank water level is maintained at 26" (which corresponds to a normal system pressure of 120 psi).
- If demand for the Golf Course irrigation can not be met, notify Water Distribution of the situation.
Low or Failed System Pressure Condition: Under certain abnormal condition (such as extreme changes in flow, a break in the main line, etc.), it is possible for the Surge Tank water level to drop below 26”. Surge Tank water levels that fall below 26” correspond to low system pressure. The fastest way to get the system back in service is to re-pressurize the Surge Tank with the portable Smith compressor and manually run the DSPS pumps. Sometimes re-pressurizing the Surge Tank alone will not re-pressurize the entire system. Under certain abnormal condition (such as extreme changes in flow, a break in the main line, etc.), it is possible for the Surge Tank water level to drop below 26”. Surge Tank water levels that fall below 26” correspond to low system pressure. Surge Tank water levels that fall below 10” require immediate action by the operator.
EQUIPMENT NAME | TAG NUMBER |
Distribution Pump #1 | 1404PMP4100 |
Distribution Pump #1 Variable Speed Drive | 1404VSD4100 |
Distribution Pump #1 Hand Switch | 1404HS4100 |
Distribution Pump #2 | 1404PMP4200 |
Distribution Pump #2 Variable Speed Drive | 1404VSD4200 |
Distribution Pump #2 Hand Switch | 1404HS4200 |
Distribution Pump #3 | 1404PMP4300 |
Distribution Pump #4 | 1404PMP4400 |
Distribution Pump #5 | 1404PMP4500 |
Surge Tank | 1404TNK4691 |
Solenoid Air Valve, Air Supply to Surge Tank | 1404FY4691 |
Surge Tank Level Sensor | 1404LE4541 |
Surge Tank Level Transmitter | 1404LIT4541 |
Surge Tank Level Display | 1404LI4541 |
Surge Tank Compressor | 1404CMP4841 |
Isolation Valve: Surge Tank and Air Receiver | 1404VLV4682 |
DSPS Air System HOA Switch | 1404HS4841 |