12 RAS Pump Start Up
Three 30 HP, variable speed, non-clog type pumps each with a capacity of 3750 gpm make up the RAS Pumping System. Two pumps provide sufficient capacity with a third provided for redundancy. The Lead/Lag/Standby status of the pumps is manually changed by the operator each month. During normal operation, RAS pumps are automatically controlled by VFDs from SCADA. Pump status, however, can be monitored at the HMI.
The primary function of the RAS Pumps is to transfer Return Activated Sludge from the Secondary Clarifiers to the Aeration Tanks.
- RAS: Return Activated Sludge
Watch for open tanks, vaults and channels. If working on or near equipment, watch for rotating parts.
- Verify that suction valve(s) are open. Verify that discharge valve(s) are open.
- Ensure that valves are completely open or closed. Valves are gear operated and take multiple turns to open or close.
- The selected RAS ratio setpoint must be accurate in order for SCADA to assign correct pumping flow rates.
Operator 1, knowledge of secondary treatment process and equipment controls.
- Record activity to log book.
- Compare flow rates with the SCADA target rate.
a. Locate the Suction Valve {tag nos. 1204VLV2100, 1204VLV2200 & 1204VLV2300}. Open the valve if it is not already open. The suction valves are located between the pump and the building wall. The valves are gear operated and will take multiple turns to open. b. Locate the Discharge Valve {tag nos. 120VLV2100A, 1204VLV2200A & 1204VLV2300A}. Open the valve if is it not already open. The discharge valves are located above the check valve. The valves are gear operated and will take multiple turns to open. 2. Prepare Pumps for Start Up at Control Panel: a. Locate the stantion with the local and Lockout Switch {tag nos. 1204HS2100A, 1204HS2200A & 1204HS2300A} and HOA Switch {tag nos. 1204HS2100, 1204HS2200 & 1204HS2300}. Verify that the Lockout Switch is in the ON position and the HOA Switch is in the AUTO position. b. At the Control Panel, locate the Main Breaker {tag nos. 1204FBK2100, 1204FBK2200 & 1204FBK2300}. Flip the switch to the ON position. c. At the Control Panel, locate the VFD Breaker {tag nos. 1204FBK2100A, 1204FBK2200A & 1204FBK2300A}. Flip the switch to the ON position. d. At the Control Panel, locate the HOA Switch {tag nos. 1204HS2100, 1204HS2200 & 1204HS2300}. Flip the switch to the AUTO position. e. Verify that the Pump On Indicator Light {tag nos. 1204YL2100, 1204YL2200 & 1204YL2300} is on. 3. Start Up Pumps from SCADA (Automatic Operation): a. At the SCADA Workstation, verify that the pumps are in AUTO mode. If the VFD HOA switches are in the AUTO position and the Lockout Switch is in the ON position, the RAS Pumps can be controlled and monitored at the SCADA workstation. b. From the SCADA screen, select the lead pump at the HOA control. SCADA will automatically assign the lag and standby pumps. The lead pump graphic will appear green on the display. c. Select the RAS ratio setpoint. This setpoint is determined by the supervisor. SCADA will automatically correct pumped flow rates to stay within a predetermined minimum and maximum range of flows. d. Compare the flow rate displayed by the magnetic flowmeter with the target rate set by SCADA. The calculation used to determine this rate is: influent flow to plant minus recycled flows that occur upstream of the secondary process. 4. Start Up Pumps from SCADA (Manual Operation): a. Locate the VFD HMI {tag nos. 1204HMI2100, 1204HMI2200 & 1204HMI2300}. b. Start the pump and adjust the pump speed. c. Locate the Pump Run Indicator Light {tag nos. 1204YL2100A, 1204YL2200A & 1204YL2300A} and verify that it is ON. 5. Observe RAS Pump Operation: a. Check that the lead pump is operating and check for proper rotation. b. If the pump is running at a high rate, the check valve should be in a “non-horizontal position”. c. Listen for excessive noise or vibration. d. Check for oil or process fluid leaks. 6. Record Data to Operator’s Log Book: Record RAS Pump Activities to the log book with other entries for the day. Include the following in the entry: · Operator(s) that performed the RAS Pump Start Up SOP. · Note condition of equipment, piping, valves, etc. · Note any unusual conditions with flows, levels, odors or other process issues. · Note any damage, wear, or required maintenance on equipment.
|
- Update log book.
- Update maintenance records (if applicable).
- Report any maintenance or attention that is required.
EQUIPMENT NAME | TAG NUMBER |
RAS Transfer Pump No. 1 | 1204PMP2100 |
RAS Transfer Pump No. 1 Motor | 1204MTR2100 |
RAS Transfer Pump No. 1 VFD | 1204VFD2100 |
RAS Transfer Pump No. 1 – Suction Valve | 1204VLV2100 |
RAS Transfer Pump No. 1 - Discharge Valve | 1204VLV2100A |
RAS Transfer Pump No. 1- Local HOA Switch | 1204HS2100 |
RAS Transfer Pump No. 1 - Local Start Switch | 1204HS2100A |
RAS Transfer Pump No. 1- Main Breaker | 1204FBK2100 |
RAS Transfer Pump No. 1- VFD Breaker | 1204FBK2100A |
RAS Transfer Pump No. 1- Bucket | 1204BKT2100 |
RAS Transfer Pump No. 1- HMI Interface | 1204HMI2100 |
RAS Transfer Pump No. 1- Indicator Light | 1204YL2100 |
RAS Transfer Pump No. 1- Run Light | 1204YL2100A |
RAS Transfer Pump No. 2 | 1204PMP2200 |
RAS Transfer Pump No. 2 Motor | 1204MTR2200 |
RAS Transfer Pump No. 2 VFD | 1204VFD2200 |
RAS Transfer Pump No. 2 – Suction Valve | 1204VLV2200 |
RAS Transfer Pump No. 2 - Discharge Valve | 1204VLV2200A |
RAS Transfer Pump No. 2- Local HOA Switch | 1204HS2200 |
RAS Transfer Pump No. 2 - Local Start Switch | 1204HS2200A |
RAS Transfer Pump No. 2- Main Breaker | 1204FBK2200 |
RAS Transfer Pump No. 2- VFD Breaker | 1204FBK2200A |
RAS Transfer Pump No. 2- Bucket | 1204BKT2200 |
RAS Transfer Pump No. 2- HMI Interface | 1204HMI2200 |
RAS Transfer Pump No. 2- Indicator Light | 1204YL2200 |
RAS Transfer Pump No. 2- Run Light | 1204YL2200A |
RAS Transfer Pump No. 3 | 1204PMP2300 |
RAS Transfer Pump No. 3 Motor | 1204MTR2300 |
RAS Transfer Pump No. 3 VFD | 1204VFD2300 |
RAS Transfer Pump No. 3 – Suction Valve | 1204VLV2300 |
RAS Transfer Pump No. 3 - Discharge Valve | 1204VLV2300A |
RAS Transfer Pump No. 3- Local HOA Switch | 1204HS2300 |
RAS Transfer Pump No. 3 - Local Start Switch | 1204HS2300A |
RAS Transfer Pump No. 3- Main Breaker | 1204FBK2300 |
RAS Transfer Pump No. 3- VFD Breaker | 1204FBK2300A |
RAS Transfer Pump No. 3- Bucket | 1204BKT2300 |
RAS Transfer Pump No. 3 - HMI Interface | 1204HMI2300 |
RAS Transfer Pump No. 3- Indicator Light | 1204YL2300 |
RAS Transfer Pump No. 3- Run Light | 1204YL2300A |